Accuracy level: 0.2S, 0.2, 0.5S Rated voltage ratio: 10000/100V, 6000/100V Rated primary current: 5~1000A Rated secondary current: 5A or 1A Rated capacity: Voltage part: 0.2 class, 20VA Current part: 0.2S, 0.2 class, 10VA Rated short-time thermal current multiple: 100I1n/1s Rated short-time dynamic stability multiple: 250I1n
1. Small size and large capacity 2. Stable insulation performance 3. Contamination-resistant, maintenance-free, long service life 4. It can be used with ZW32-12 outdoor circuit breaker to form the main part of the prepaid management system. 5. The box body is welded by stainless steel, the product is beautiful as a whole and has no hidden danger of leakage and rain. Conditions of Use: 1. JLSZY-10 integral casting high voltage dry type combined transformer (integral casting high voltage metering box) is suitable for 10kV or 6kV three-phase AC power system with a frequency of 50Hz; 2. Ambient temperature: -40℃~+40℃; 3. The relative humidity of the air: the monthly average value is less than or equal to 90%; 4. Altitude: no more than 2000m; 5. The surrounding air should not be polluted by corrosive gas or flammable gas; 6. Creepage distance: 340mm.